6-10KV Oil-Immersed Power Distribution Transformer
Product features
The three-phase oil-immersed distribution voltage device produced by our company adopts a new insulation structure,which improves the short-circuit resistance;The iron core is made of high-quality cold-rolled silicon steel sheets;High-voltage windings are made of high-quality oxygen-free copper wires and adopt multi-layer cylindrical structure;All fasteners are treated with special anti-corrosion treatment.Adopt corrugated oil tank and fully sealed structure.
The product has the characteristics of high efficiency and low loss,which can save a lot of money and operating costs,and has remarkable social benefits.It is a high-tech product promoted by the state.
Reliable structure
On the basis of traditional structure and mature technology,our company has made
many improvements,such as adopting:
① Spiral coil with longitudinal oil passage has better internal heat dissipation
② The effective support of the coil end face is improved,and the short-circuit current resistance is stronger;
③ New hoisting structure and positioning structure are adopted to ensure more reliability in long-distance transportation and operation;
④ We also have many unique and reliable structures to serve you;
⑤ Choosing a transformer with higher performance level will have a higher level of technical content
⑥ The oil tank adopts fully sealed structure to isolate the transformer from the atmosphere,prevent and slowdown the deterioration of oil and damp insulation, enhance the operation reliability and avoid maintenance during normal operation.
High quality materials
All raw materials have undergone quality inspection,and all raw material manufacturers have undergone strict examination according to the national standard Iso9000.
① The oxygen-free copper wire with lower resistivity is selected,and after a series of additional surface treatments,it is smoother and has no burr sharp corners,which makes the load loss of the transformer lower and the electrical performance more reliable.
② Select high-quality silicon steel sheet,and with the improvement of performance level,adopt silicon steel sheet with lower unit loss,so that the no-load loss of transformer is lower
③ Select high-quality laminated wood insulation,which will never crack,even under the action of short-circuit current
④ The transformer oil after deep filtration is selected,which has a lower level of water gas and impurities,and the transformer works more reliably.
⑤ Select high-quality rubber sealing material to effectively prevent aging and earth leakage
Normal service conditions
Altitude
No more than 1000m;
Environmental temperature:
The maximum temperature is+40℃;
The maximum monthly average temperature is +30℃;
The maximum annual average temperature is +20℃;
The outdoor minimum temperature is -25℃。
The waveform of power supply voltage is similar to sine wave.
For three-phase transformer,its three-phase supply voltage should be approximately symmetrical. Installation environment:
There is no obvious pollution in the installation environment;
The ground acceleration ag caused by earthquake is lower than 3m/s²in the horizontal direction and 1.5m/s² in the vertical direction.
Special Conditions of Use
Any special use conditions that need to meet the normal use conditions of the transformer shall be stated in the inquiry and order.
Executive standard
GB/T1094.1 GB/T1094.2 GB/T1094.3 GB/T1094.5
GB/T25289 GB/T6451 GB/T7595 GB20052
JB/T3837 JB/T10088 IEC60076
The transformer products produced by our company all meet the latest version of the above standards.
Ordering instructions
When ordering,the product model,rated capacity,rated voltage of high and low voltage,high voltage distribution range,phase number,frequency,connection group label,etc.shall be provided.
Model and meaning
Technical parameter
Technical parameters of 6kV and 10kV S11 series oil-immersed non-excitation voltage regulating distribution transformer
Rated capocltv kVA | Voltage combination LV | Connecting group | Loss kW | Short circui impedance % | Weight kg | Overall dimensior Length *Width *Height | Gauge Vertical Horizontal | ||||||
High volta ge | High yoltage tap range | Low yoltage | No-load | Lood 75℃ | Body weight | Oil weight | Total welgh | ||||||
30 | 6 6.3 10 10.5 |
±2×2. 5% ±5% |
0.4 | Dyn11 Yzn11 YynO |
0.100 | 0.630 | 0.600 | 4.00% | 135 | 55 | 325 | 680*480*846 | 550/400 |
50 | 0.130 | 0.910 | 0.870 | 210 | 75 | 435 | 765*690*876 | 550/400 | |||||
63 | 0.150 | 1.09 | 1.04 | 245 | 85 | 490 | 795*645*915 | 550/400 | |||||
80 | 0.180 | 1.31 | 1.25 | 290 | 90 | 550 | 825*660*925 | 550/550 | |||||
100 | 0.200 | 1.58 | 1.50 | 315 | 95 | 590 | 810*770*890 | 550/550 | |||||
125 | 0.240 | 1.89 | 1.80 | 365 | 100 | 660 | 825*800*960 | 550/550 | |||||
160 | 0.280 | 2.31 | 2.20 | 440 | 115 | 720 | 1115*735*985 | 550/550 | |||||
200 | 0.340 | 2.73 | 2.60 | 490 | 160 | 790 | 1186*815*1050 | 550/550 | |||||
250 | 0.40C | 3.20 | 3.05 | 600 | 150 | 960 | 1290*860*1050 | 660/660 | |||||
315 | 0.48C | 3.83 | 3.65 | 710 | 180 | 1120 | 1350*920*1090 | 660/660 | |||||
400 | 0.570 | 4.52 | 4.30 | 920 | 210 | 1440 | 1485*1030*1120 | 660/660 | |||||
500 | 0.680 | 5.41 | 5.15 | 1050 | 320 | 1800 | 1485*1030*1160 | 660/660 | |||||
630 | Dyn11 YynO |
0.810 | 6.20 | 6.20 | 4.50% | 1130 | 260 | 1770 | 1550*1045*1225 | 660/660 | |||
800 | 0.98C | 7.50 | 7.50 | 1340 | 290 | 2060 | 1730*1220*1285 | 820/820 | |||||
1000 | 1.150 | 10.3 | 10.3 | 1440 | 420 | 2505 | 1670*1160*1375 | 820/820 | |||||
1250 | 1.360 | 12.0 | 12.0 | 1750 | 480 | 2970 | 1750*1240*1425 | 820/820 | |||||
1600 | 1.640 | 14.5 | 14.5 | 2240 | 600 | 3950 | 1860*1250*1485 | 820/820 | |||||
2000 | 1.940 | 18.3 | 18.3 | 5.00% | 2575 | 635 | 4305 | 1990*1315*1620 | 820/820 | ||||
2500 | 2.290 | 21.2 | 21.2 | 3270 | 815 | 5440 | 2065*1360*1750 | 1070/1070 |
Note:
① For three-phase transformers with rated capacity of 500kVA or less,the load loss value above diagonal line in the table is applicable to Dyn11 or Yzn11 connection group,and the load value below diogonal line is applicable to Yyn0 connection group;
② When the average annual load rate of transformer is between 35%and 40%,the highest operating efficiency can be obtained by using the losses in the table
Technical parameters of 6kV and 10kV S13 series oil-immersed non-excitation voltage regulating distribution transformer
Rated capoclty kVA | Voltage combination | Connecting group | No-load | Loss kW | Short circui impedance % | Weight kg | Overall dimension Length *Width *Height | Gauge Vertical Horizontal | |||||
High voltage | High yoltage taprange | Low yoltage | Lood 75℃ | Body weight | Oil weight | Total welgh | |||||||
30 | 6 6.3 10 10.5 |
±2×2. 5% ±5% | 0.4 | Dyn11 Yzn11 YynO |
0.080 | 0.630 | 0.600 | 4.00% | 140 | 60 | 280 | 700*545*855 | 550/400 |
50 | 0.100 | 0.910 | 0.870 | 210 | 80 | 370 | 750*645*915 | 550/400 | |||||
63 | 0.110 | 1.09 | 1.04 | 240 | 90 | 440 | 790*645*915 | 550/400 | |||||
80 | 0.130 | 1.31 | 1.25 | 260 | 90 | 480 | 805*706*930 | 550/550 | |||||
100 | 0.150 | 1.58 | 1.50 | 350 | 110 | 600 | 850*685*1075 | 550/550 | |||||
125 | 0.170 | 1.89 | 1.80 | 380 | 110 | 645 | 850*790*975 | 550/550 | |||||
160 | 0.200 | 2.31 | 2.20 | 500 | 130 | 790 | 880*860*1050 | 550/550 | |||||
200 | 0.240 | 2.73 | 2.60 | 540 | 160 | 870 | 1180*791*1090 | 550/550 | |||||
250 | 0.290 | 3.20 | 3.05 | 670 | 170 | 1050 | 1270*850*1140 | 660/660 | |||||
315 | 0.340 | 3.83 | 3.65 | 750 | 180 | 1150 | 1320*900*1160 | 660/660 | |||||
400 | 0.410 | 4.52 | 4.30 | 905 | 210 | 1370 | 1390*9501*215 | 660/660 | |||||
500 | 0.480 | 5.41 | 5.15 | 1120 | 240 | 1680 | 1420*950*1280 | 660/660 | |||||
630 | Dyn11 YynO |
0.570 | 6.20 | 6.20 | 4.50% | 1330 | 280 | 1960 | 1490*1000*1340 | 660/660 | |||
800 | 0.700 | 7.50 | 7.50 | 1400 | 300 | 2150 | 1640*1155*1350 | 820/820 | |||||
1000 | 0.830 | 10.3 | 10.3 | 1510 | 350 | 2410 | 1660*1155*1380 | 820/820 | |||||
1250 | 0.970 | 12.0 | 12.0 | 1720 | 440 | 2860 | 1720*1250*1480 | 820/820 | |||||
1600 | 1.170 | 14.5 | 14.5 | 2285 | 590 | 3745 | 1840*1340*1560 | 820/820 | |||||
2000 | 1.550 | 18.3 | 18.3 | 5.00% | 2554 | 730 | 4289 | 2010*1370*1660 | 820/820 | ||||
2500 | 1.830 | 21.2 | 21.2 | 2995 | 810 | 5170 | 2020*1370*1850 | 1070/1070 |
Note:
① For three-phase transformers with rated capacity of 500kVA or less,the load loss value above diagonal line in the table is applicable to Dyn11 or Yzn11 connection group,and the load value below diogonal line is applicable to Yyn0 connection group;
② When the average annual load rate of transformer is between 35%and 40%,the highest operating efficiency can be obtained by using the losses in the table