ZGS- 35 /0.8Wind Power Combined Substation

Scope of application
ZGSD-Z·F-/35 series combined transformer is a special equipment for grid output after raising  the voltage of 0.6-0.69kV from wind turbine to 35kV.The product is the high-voltage load switch, fuse transformer body and other components sealed  in the same box,using the transformer insulation liquid as the insulation and heat dissipation medium of the whole product.The product  has the characteristics of compact structure,small volume,easy installation,suitable for all kinds of wind power generation sites,is an important supporting equipment of wind power generation  System

    General Introduction

    General Introduction

    The ZGSD-Z·F-/35 Series Combined Transformer is a high-integrity power distribution solution designed for 35kV medium-voltage systems. Integrating high-voltage switchgear, a power transformer, and low-voltage distribution panels into a single enclosed structure, it offers compact installation, reliable operation, and minimal maintenance. The "F" in the model denotes forced air cooling (AF), enhancing heat dissipation for continuous heavy-load applications. Ideal for urban grids, industrial parks, and renewable energy projects, this transformer combines safety, efficiency, and modular design.

    Technical Parameters

    Parameter Specification
    High-Voltage Rating 35kV (primary)
    Low-Voltage Rating 0.4kV–10kV (secondary, customizable)
    Power Rating 1000kVA–6300kVA
    Frequency 50Hz/60Hz
    Cooling Method ONAN/ONAF (Oil Natural Air Natural/Forced Air)
    Insulation Class F (temperature rise ≤100K)
    Impulse Withstand Voltage 170kV (lightning impulse)
    Short-Circuit Impedance 6.5%–8% (depending on capacity)
    Protection Level IP54/IP65 (weatherproof)
    Noise Level ≤65dB (at full load)

    额定容量 
    rated capacity KVA
    电压组合及分接范围                          Voltage combination and tap range 联结组标号Connection Group Symbol  空载损耗  No-load Loss        (W) 负载损耗 Load Loss        (W) 空载电流No-load Current   (%) 短路阻抗Short Circuit Impedance  (%)
    高压      high voltage 
    KV
    分接范围 Tap Range 低压         low voltageKV
    30 10
    6.6         6.3           6
    ±5         ±2×2.5% 0.4 Yyn0   Dyn11 170 760 2.40  4
    50 240 1070 2.40  4
    80 330 1480 1.80  4
    100 360 1690 1.80  4
    125 420 1980 1.60  4
    160 480 2280 1.60  4
    200 550 2710 1.40  4
    250 640 2960 1.40  4
    315 790 3730 1.20  4
    400 880 4280 1.20  4
    500 1040 5230 1.20  4
    630 1200 6290 1.00  4
    630 1170 6400 1.00  6
    800 1360 7460 1.00  6
    1000 1590 8760 1.00  6
    1250 1880 10370 1.00  6
    1600 2200 12580 1.00  6
    2000 2740 15560 0.80  6
    2500 3240 18450 0.80  6

    Key Features

    1. Integrated Design
      • Combines transformer, HV switchgear (RMU/VCB), and LV distribution in a single enclosure.
      • Reduces installation time by 50% compared to traditional separate systems.
    2. Forced Air Cooling (AF)
      • Enhanced heat dissipation for 15%–20% higher overload capacity.
      • Auto-start fans based on temperature sensors for energy efficiency.
    3. High Safety Standards
      • Oil-immersed transformer with Buchholz relay and pressure relief device.
      • SF6 or vacuum circuit breakers for arc protection.
    4. Low Loss & Energy Efficiency
      • High-grade silicon steel core reduces no-load losses by 30%.
      • Meets IE3 efficiency standards (GB/T 20052-2020).
    5. Short-Circuit Resistance
      • Robust winding structure withstands 25kA short-circuit current for 2 seconds.
      • Reinforced core clamping to prevent mechanical deformation.
    6. Modular & Customizable
      • Optional on-load tap changer (OLTC) for ±2.5% voltage regulation.
      • Configurable LV panels with MCCB, power factor correction, and metering.
    7. Environmental Adaptability
      • Corrosion-resistant steel shell for coastal or industrial environments.
      • -25°C to +55°C ambient temperature operation.

    System Configuration

    1. High-Voltage Section

    • Ring main unit (RMU) with load break switches and fuses
    • Vacuum circuit breaker (VCB) option for fault protection
    • Surge arresters and current transformers (CTs)

    2. Transformer Section

    • 35kV oil-immersed transformer with copper windings
    • Conservator tank with oil level gauge and breather
    • PT100 temperature sensors for winding and oil monitoring

    3. Low-Voltage Section

    • Distribution panels with MCCB/MCB circuit breakers
    • Power quality monitoring devices (voltage/current meters)
    • Optional PLC-based control system for remote monitoring

    4. Protection & Monitoring

    • Differential protection relay for transformer faults
    • SCADA interface for real-time data transmission
    • Remote alarm via GSM/GPRS (optional)

    Leave Your Message